  1. Make sure that the generator circuit breaker is open (if the generator does not have a circuit breaker: make sure that the installation main breaker is open).
  2. Check the oil level.
  3. Check the fuel level.
  4. Check the water level (for water-cooled generators only).
  5. Make sure that there is no leakage (no oil or fuel under the generator).
  6. Start the generator.
  7. Wait 2 minutes.
  8. Close the circuit to the main circuit of the office or compound.
  9. Record time of start on the associated log booklogbook.

Standard stopping procedure:

  1. Warn users that the power will be cut.
  2. Open the generator circuit breaker (if the generator does not have a circuit breaker: open the installation main breaker).
  3. Wait 2 minutes and.
  4. Stop the generator.
  5. Record time of stoppage on the associated log booklogbook.
  6. Refuel if necessary.

Care & Maintenance

...

To size a battery system, the following will be need to be determined:

  • The maximum power the inverter has to be able to deliver to the installation.
  • The amount of energy that must be stored in the battery to cover your needs.
  • In some case, the power the charger can deliver to the batteries.

...